Super wide input voltage range -60%~+25% for high grid adaptability and prolong battery service life.
Dual DSP control for top performance and reliability.
Intelligent fan speed control reduces the noise and prolongs fan service life.
Anti-corrosion resistant coating in all PCB boards.
Full protection with input, output, bypass, maintenance bypass and battery breaker.
Generator compatible ensure the clean power for extend power outage.
Local and remote EPO function for immediately remove power from connected load in the event of emergency.
Short circuit time settable 10-200ms which provide high protection for system.
Bus synchronization control function provides reliable high power for the dual bus application.
Output power factor 1.0, more powerful to connect more critical loads.
AC/AC efficiency up to 96% and 25% load above 94% efficiency
reduces heat dissipation and limits power consumption costs.
ECO mode efficiency up to 99% will significantly reduce the TCO.
3 level inverter and IGBT technology ensure input PF>0.99 and low THDi <3% for maximum upstream sources compatibility.
Self-load test function, easy debugging and easy onsite test during commissioning, before it is connected the real load, without using costly temporary loads, cabling and breakers for energy saving.
Multi-functional touch screen with LED Indicators, ensure comprehensive and visualized information display.
Large data storage capacity, events logs 10000pcs.
Intelligent battery management which include 3 stage battery charging mode, Battery static and battery test function which prolong battery service life.
Key components pre-alarm function.
Smart programmable dry contact communication.
Dedusting function which save the service time and keep system performance.
Easy onsite firmware update.
Isolation transformer can house inside the cabinet for full input or output isolation which suitable for medical and critical application.
Isolation transformer temperature detection and alarm.
Short circuit protection, restrain the high current puncture to UPS.
No effects to the UPS output performance or reduced impact of the inverter power components whilst supplying specific loads.
Adjustable input and output phase 3:3/3:1/1:1 for 10- 20KVA and 3:3/3:1 for 30-40KVA to meet multiple power distribution condition.
Integrated autonomy with compact footprint and external battery slot for extend power outage.
DC voltage settable ±96~±240 for 10KVA, ±144 ~±240 for 20~40KVA.
Multi-language of Chinese, English, Italian, Polish, Spanish, Korean.
Frequency converter function(60Hz/50Hz or 50Hz/60Hz).
Common battery bank in 2 units parallel system
Easy onsite parallel slot modification up to 4 units
Wheel design easy for movement and relocation.

- MY10/
- MY15/
- MY20/
- MY30/
- MY40
Myria Series
ZOOM
DRAG TO ROTATE