KR11T Series 6-10kVA
· Computer room
· Data center
· Point-of-sale
· Router
· Hub and other network device
· Commercial facility
· Precision instrument
Advanced Technology
● Online double conversion
● High input power factor
● EPO for 5kVA
High Reliability
● Wide input voltage range
● Full protection function
● High reliability and performance
● Manual bypass switch optional for 5kVA
Excellent Flexibility
● Intelligent RS232 communication port
● UPS management software (optional)
● SNMP or USB or dry contact (optional)
● External battery bank (optional)
MODEL | KR6000T(L) | KR1110T(L) |
---|---|---|
INPUT | ||
Voltage (Vac) | 80~275 | |
Frequency (Hz) | 50/60±10% (50/60Hz auto-sensing) | |
Power Factor | ≥0.99 | |
THDi | <5% (linear load) | |
Phase | 3W (L+N+G/L1+L2+G) | |
OUTPUT | ||
Capacity (kVA) | 6 | 10 |
Power Factor | 0.9 (1 optional) | |
Voltage (Vac) | 120/208/220/230/240±1% (settable on display panel and output wiring line) | |
Frequency (Hz) | 50/60±0.2% (battery mode) | |
THDv | THD<1% (linear load), THD<4% (nonlinear load) | |
Transfer Time (ms) | 0 | |
Max. Efficiency | 93.5% | |
Crest Factor | 3:1 | |
Overload | 105%<Load≤130%:10mins,130% | |
BATTERY | ||
Battery Voltage (Vdc) | 192 (192~240V settable) | |
Battery Type | 16×7Ah12V/External | 16×9Ah12V/External |
Charging Current (A) | 1A (default); 1~8A settable (external battery) | |
GENERAL | ||
Communication Interface | RS232, EPO(SNMP, USB, RS485+dry contact, Protocol transfer kit are optional in slot) | |
LCD Display | AC input & output voltage, frequency, load level, battery level, temperature; AC mode, battery mode, bypass mode, and fault | |
Alarm | Low battery, abnormal AC input, UPS failture, etc. | |
Protection | Low battery, overload, short-circuit and over temperature, etc. | |
Noise (dB) | 50 | |
Working Temperature (°C) | -5~40 | |
Relative Humidity | 0~95%, no condensation | |
Dimension (W×D×H) (mm) | 250×660×720 | |
Weight (Kg) | 96/60 | 113/73 |